|
| |
Nuclear
Instrumentation
The following descriptions are an example of the detail which the Exitech
Nuclear Instrumentation models achieve.
Local Power Range Monitor
The Limerick Local Power Range Monitor (LPRM) consists of forty-three
LPRM neutron detector string assemblies located in various core
positions, with each detector string having four LPRM neutron detectors.
Each of the 172 detectors is grouped in one of eight channels: LPRM
groups A or B, or APRM channels A through F. Each channel is composed of
either twenty-one or twenty-two LPRM in-core neutron detectors. The
plant LPRM system receives inputs from the neutron detectors and
provides outputs to the computer, the Rod Block Monitor (RBM) selection
matrix, to the Average Power Range Monitor (APRM) system, and to upscale
and downscale alarm trip circuits. The simulated LPRM system (see Figure
3.1) outputs to the APRM and alarm trip circuits; however the selection
matrix interface is handled by the APRM system. The following discussion
concerns the processing of the individual LPRM neutron detector signals
and the processing of outputs within the LPRM system. Reference
C51-1080-E-011, 13, 15, 17, 19, 21, 27, and 28.
Each LPRM in-core neutron detector (an ionization chamber) in the
plant is connected to a signal string containing an ion chamber power
supply and flux amplifier, all in series. The neutron flux will ionize
the gas in the ionization chamber, changing the resistance between two
electrodes. The current between the electrodes will affect the voltage
output from the flux amplifier. This voltage output (which will actually
be a normalized variable in the simulated system) will then be sent to
the computer, RBM, upscale and downscale trip circuits, and APRM system.
The upscale trip circuit is modeled in the LPRM system and compares
the output of the flux amplifier to a reference voltage. When the
reference voltage is exceeded the following will happen : the trip
circuit is actuated; a manually reset trip circuit will light an upscale
light on backpanel P607 (for APRM F); an auto reset trip which goes to
the annunciator, and an auto reset trip which lights an upscale light on
panel 649. The manual reset trip can be reset from backpanel P607, for
APRM F. The operation of the downscale trip circuit is the same as the
upscale trip circuit, except that the circuit is tripped when the flux
amplifier output becomes less than the downscale reference voltage.
Each LPRM card in the plant has an BYPASS/CALIBRATE/OPERATE switch
for that particular LPRM. The OPERATE position will connect the LPRM to
its normal configuration. The CALIBRATE and BYPASS positions will
connect the flux amplifier input to a calibration current source; 0
volts will be connected to the RBM and computer outputs, and -15 volts
will be connected to the meter function switch S3. Meter function
switches S2 and S3 will select a particular LPRM to be displayed on the
LPRM meters. If the selected LPRM is in BYPASS or CALIBRATE mode, then
-15 volts is provided to the calibrator and the calibrator provides a
calibration current to the selected LPRM. A summary of the plant
switches and potentiometers for each LPRM is as follows :
- BYPASS/CALIBRATE/OPERATE switch ZxxS1 (on the LPRM card)
connects the input to the flux amplifier. This switch is simulated
with remote functions 12, 13, and 14. These remote functions will
place in bypass an LPRM which has malfunction 12, 13, or 15,
respectively, applied.
- Range switch S1 selects high, low, and medium range
potentiometers to change the gain of the flux amplifier. This switch
is not simulated.
- Gain controls R1, R2, R3 will adjust the gain of the LPRM
card for the high, medium, and low ranges. These controls are not
simulated.
- Gain controls R4 and R5 will adjust the upscale and downscale
trip reference points. These controls are not simulated.
The above explanation of the LPRM card and associated outputs was
given in reference to plant operation. In the simulator, the LPRM cards
are not mounted in backpanel P607. The bypass function of the LPRM cards
are simulated with remote functions 12, 13, and 14.

Average Power Range Monitor
The APRM system module will include simulation for two primary
subsystems : the APRM subsystem and the Flow Unit subsystem. Each is
explained separately.
APRM Subsystem
The plant APRM subsystem consists of APRM channels A through F.
Each APRM channel takes the signals (twenty-one or twenty-two) from
the associated LPRM flux amplifier and processes those signals,
along with test signals from backpanel P607. The simulated APRM
system includes not only APRM channels A through F, but also LPRM
groups A and B after the flux amplifier. All 172 flux amplifier
voltage outputs are normalized and are simulated in the LPRM module.
The LPRM module also includes computer outputs, RBM outputs, and
alarm outputs which come from the LPRM cards. The APRM module
receives the flux amplifier output from the LPRM module, and
simulates the following :
- APRM Averaging Circuit (reference C51-1080-E-12, 14, 16,
18, 20, and 22)
- APRM Trip Reference Circuit (reference C51-1080-E-041 and
43)
- APRM Channel Trip Circuit (reference C51-1080-E-012, 14,
16, 18, 20, and 22)
- APRM/LPRM Channel Calibration and Test Circuit and Meter
Output (reference C51-1080-E-026)
- APRM Bypass Circuits (reference C51-1080-E-023 and 24)
- APRM Channel Relay Circuit Outputs (reference
C51-1080-E-023, 24, 25, 26, 44, 45, 46, 47, and 48)
- APRM Averaging Circuit
Each LPRM in the operate mode will be connected to the APRM
averaging circuits, card Z29 and Z30 in the plant. A minimum of
fourteen LPRMs are required for the APRM averaging circuit to be
functional. The averaged power output from the averaging circuit
goes, through aux unit Z31, to the APRM trip circuits (quad trip
unit Z35), to the Rod Block Monitor channels, and to the computer,
recorders, and meters. Trip circuits in turn will go to control
relays which will provide signals to the Reactor Protection System (RPS),
to Reactor Redundant Control Systym (RRCS), and to alarm circuits.
The count circuit is a part of aux unit Z31 and is also simulated.
The total count of all LPRMs in an APRM are put together and output
to (1) APRM channel mode selector switch to APRM meter, and (2) INOP
trip circuit on Z35. The APRM meter will read the total number of
LPRMs in OPERATE position when the P607 selector switch S3 is
selected to COUNT. Each operating LPRM gives 5% of total indication.
The output provided to the INOP trip circuit will be reduced below
the acceptable limit (non-adjustable) if less than fourteen LPRMs
are being averaged in the APRM. See Figure 3.2 for the averaging
circuit.
- APRM Trip Reference Circuit
Each of six APRM channel (and not the two LPRM channels) receives
an input signal of 0 to 125% flow from the flow channels of the Flow
Unit subsystem. The lowest of the values is selected in the low
auctioneer circuit Z34 (bypassed flow channels will go in with a
high signal so that low auctioneer will choose the unbypassed
channel). The output from the low auctioneer goes through the APRM
mode selector switch on backpanel P607 to the flow control trip
reference unit Z33, from which outputs go to the upscale alarm quad
trip unit Z35A, to the upscale neutron trip quad trip unit Z35B, and
to the power range recorders (if so switched). Reference voltages
for the quad trip circuits are calculated using two types of
adjustment, slope and level. The trip reference circuit uses the
trip setdown; if the reactor mode switch is in any position other
than run, the dc reference voltage from the trip reference unit is
reduced, representing lower power levels to the upscale neutron trip
and upscale alarm trip circuits. See Figure 3.3 for the trip
reference circuit.
- APRM Channel Trip Circuit
In the plant there are two types of channel trip circuits. One
type is actuated from the flux amplifier output on each LPRM card,
and one type is actuated from the APRM averaged output signal. The
simulated APRM channel trip circuits consist of the Quad Trip card
trip circuits Z35A,B,C,D, all of which are simulated. The outputs
from the both the quad trip units go to panel lights, and also to
relays which go to RPS and annunciators and the computer. See Figure
3.2 for the quad trip circuits.
- APRM/LPRM Channel Calibration and Test Circuit and Meter
Output
Each APRM and LPRM channel has a backpanel P607 meter to display
selected LPRM output. Only APRM F and LPRM A have a simulated meter;
see Figure 3.5. The meter/switch functions are simulated as follows
(switch designations may be found in GEK-75715, "Power Range
Neutron Monitoring System Operation and Maintenance
Instructions") :
The following switches are part of meter panel Z36
- Mode switch S1 selects OPERATE, STANDBY, ZERO, PWR, OR
PWR-FLOW positions. The test position PWR will connect the R2
(POWER) potentiometer so that the potentiometer value takes the
place of the APRM channel outputs, and test position PWR-FLOW
will connect the R3 (FLOW) potentiometer to the flow control
trip reference card and APRM channel trip circuits. LPRM
channels do not have a functional switch. Mode switch S1 is not
simulated in Limerick.
- Meter function switches S2 and S3 will select the LPRM to
output to the meter. Switch S3 can also select COUNT (number of
LPRMs operational), FLOW (display output of flow unit on meter),
or AVERAGE (display average power on meter). This switch is
simulated for all positions for APRM F and LPRM A, except that
LPRM channels do not have the COUNT, FLOW, and AVERAGE positions
functional.
- Meter switch S4 provides EXPAND, NORMAL, and REVERSE
functions, with EXPAND and REVERSE providing X 10 expansion.
Meter switch S4 is not simulated for Limerick.
- Monitor switch S5 will select -10 volts output from the
calibrator circuit. Calibration current switch S7 (see below) is
not simulated; therefore selection of the monitor switch will
not affect output of the meter (assume calibration is constant).
The ADJUST potentiometer R1 is not simulated.
- Reset switch S6 is a momentary pushbutton which will
reset any tripped latching circuits if trip condition has
returned to normal. The switch is simulated for APRM F and LPRM
A.
- Calibration current switch S7 is present in the plant,
however it is not present in the simulator and is therefore not
simulated for any LPRM or APRM channel.
- Inop inhibit switch S8 will enable the operator to check
the system trips even if the APRM mode switch S1 is not in
OPERATE position. Inop inhibit switch S8 is not simulated for
Limerick.
- APRM Bypass Circuits
There are two bypass switches on panel 603 which will bypass one
and only one APRM channel. One bypass switch will bypass either APRM
channels A, C, or E, and the second bypass switch will bypass either
APRM channels B, D, or F. The APRM C and D averaged core power is
output to RBM channel A and B respectively. When the particular APRM
channel is bypassed, the RBM channel will read APRM E (instead of C)
and APRM F (instead of D). See Figure 3.4 for bypass signals.
- APRM Channel Relay Circuit Outputs
The LPRM card upscale and downscale trip circuit outputs, and
quad trip module trip circuit outputs will control relays contained
on the plant ICPS page. All of these outputs are modeled in the APRM
module, except that the LPRM card outputs and associated relays K13
and K15 actuation are modeled in the LPRM module. The upscale,
downscale, and inop circuits in the APRM system are applied in
series with the RBM upscale, downscale, and inop circuitry to
provide rod withdrawal blocks to the Reactor Manual Control System (RMCS).
If any of the rod withdrawal inhibit relays are deenergized, then a
rod block is imposed by the RMCS system and cannot be cleared until
the cause in the APRM or RBM system is cleared. All other
interfaces, including RPS, RRCS, annunciator, computer, and lights,
are simulated. See Figure 3.4 for APRM aux relays.
Flow Unit Subsystem
The Flow Unit subsystem is composed of four flow channels, A
through D. Each flow channel has flow transmitters, a flow unit (ARxx),
associated lights and indicators, and bypass logic (resident in
panel 603). The flow unit has a square root converter, a summer,
trip circuitry, and amplifiers. Instead of doing a square root
conversion of the recirc differential pressure, the simulated system
will directly use a flow variable. The summer will pass the summed
flow (after various mode switch and interlock processing) on to the
low auctioneer circuit in the APRM subsystem. The summed flow will
also go to the upscale trip circuit and the comparator circuit in
the flow unit. The comparator circuit compares the output of its
flow unit with the output of the paired flow unit (the summed flow
from A goes to B, B to D, D to C, C to A). The circuit provides trip
outputs when the difference between the paired units exceeds a
predetermined setpoint. If a flow unit is bypassed, the signal which
is input to it will be passed to the receiving flow unit (for
example, if channel D is bypassed, then the summed signal from flow
unit B will be passed to flow unit C for comparison). The output
from the comparator, as well as the upscale trip, will actuate
relays which give a rod block. The signals from these two will also
go to lights, alarms, and the computer. See Figure 3.6 for the flow
channel simulation diagram.

Rod Block Monitor
The RBM system provides in-core monitoring during power
operation. The system provides the operators with accurate and
timely information pertinent to its status. This information is
provided on a continuous basis so that the operator can have a
high degree of confidence that the RBM function is available and
operating properly.
The RBM channels operate when the reference Average Power
Range Monitor (APRM) is indicating greater than 30 percent.
Following a new rod selection, the RBM selects and averages the
Local Power Range Monitors (LPRM) around the newly selected
control rod. A trip signal is generated if this average LPRM
value is greater than the power biased trip setpoint. Note,
either of the two channels may be bypassed at any time.
The RBM system includes signal conditioning equipment,
averaging circuits, trip circuits, power supplies, a channel
bypass switch, and readout equipment. The trip reference of the
RBM trip unit is set to ensure that the Neutron Monitoring
System (NMS) can block a control rod withdrawal in response to
high local neutron flux during reactor power operation. This
could result from a control rod withdrawal due to an operator
error or equipment malfunction, to which RBM signals respond and
prevent local fuel damage and/or a Reactor Protection System (RPS)
scram if allowed to proceed.
The software effecting the APRM, RBM, & Technical
Specification/Maximum Extended Load Line Limit Analysis (ARTS/MELLLA)
modification will be included in this upgrade and by replacing
the existing flow biased trip signals with power dependent trip
setpoints. Also, some unnecessary indication will be deleted.

|